Model D1000-D2000 Model D3000 – D3300
|
Installation Steps
Note: When models include heat trace groves, the number and location may vary. Check with design drawings for exact number and location. |
Table 1 Bolt Torque |
|||||
D1000 (Series) | D2000 (Series) | D1000 (Series) | D2000 (Series) | ||
Pipe Size | Bolt Torque (FT – LBS) |
Bolt Torque (FT – LBS) |
Pipe Size | Bolt Torque (FT – LBS) |
Bolt Torque (FT – LBS) |
1/2″ | 1-3 | 1-3 | 2 1/2″ | 2-4 | 2-4 |
3/4″ | 1-3 | 1-3 | 3″ | 3-5 | 3-5 |
1″ | 1-3 | 1-3 | 3 1/2″ | 3-5 | 3-5 |
1 1/4″ | 1-3 | 1-3 | 4″ | 3-5 | 3-5 |
1 1/2″ | 1-3 | 1-3 | 6″ | 3-5 | 3-5 |
2″ | 2-4 | 2-4 |
Table 2 Bolt Torque |
||||
D3000 Series | D3100 Series | D3200 Series | D3300 Series | |
Pipe Size | Bolt Torque (FT – LBS) |
Bolt Torque (FT – LBS) |
Bolt Torque (FT – LBS) |
Bolt Torque (FT – LBS) |
1 | 1-3 | 1-3 | 1-3 | 1-3 |
1.5 | 1-3 | 1-3 | 1-3 | 1-3 |
2 | 1-3 | 1-3 | 1-3 | 1-3 |
2.5 | 1-3 | 1-3 | 1-3 | 1-3 |
3 | 1-3 | 1-3 | 1-3 | 1-3 |
3.5 | 1-3 | 1-3 | 1-3 | 1-3 |
4 | 1-3 | 1-3 | 1-3 | 1-3 |
5 | 8-10 | 8-10 | 8-10 | 8-10 |
6 | 8-10 | 8-10 | 8-10 | 8-10 |
8 | 8-10 | 8-10 | 20-22 | 20-22 |
10 | 13-15 | 13-15 | 28-30 | 28-30 |
12 | 13-15 | 13-15 | 28-30 | 28-30 |
14 | 13-15 | 13-15 | 28-30 | 28-30 |
16 | 13-15 | 13-15 | 28-30 | 28-30 |
18 | 13-15 | 13-15 | 28-30 | 28-30 |
20 | 13-15 | 13-15 | 28-30 | 48-50 |
24 | 13-15 | 13-15 | 28-30 | 48-50 |
26 | 13-15 | 13-15 | 28-30 | 48-50 |
28 | 13-15 | 13-15 | 28-30 | 48-50 |
30 | 13-15 | 13-15 | 28-30 | 48-50 |
32 | ||||
36 | 33-35 | 42-44 | ||
42 |