< Back to Pipe Anchors
Model C3100 - Insulated Friction Pipe Anchor |
Download PDF
Dimensions and ratings are subject to change without notice.
The load ratings represent average values obtained in accordance with accepted test methods and are subjected to normal manufacturing variations.
Note: For higher load ratings, see: C3200, C4100.
Installation Instructions
Pipe Size |
Load Rating |
Insul Thk. = 1" |
Insul Thk. = 1-1/2" |
Insul Thk. = 2" |
Insul Thk. = 2-1/2" |
Insul Thk. = 3" |
Insul Thk. = 4" |
Insul Thk. = 5" |
Vert. lb. |
Axial lb. |
B |
C |
E |
B |
C |
E |
B |
C |
E |
B |
C |
E |
B |
C |
E |
B |
C |
E |
B |
C |
E |
1/2
3/4
1
1 1/2 |
280
350
450
650 |
56
70
90
130 |
4
4
4
4 |
1.5
1.5
2
2 |
3.25
3.25
3.875
4.5 |
4
4
4
4 |
2
2
2.5
2.5 |
4.375
4.375
5
5.5 |
4
4
4
4 |
2.5
2.5
3
4 |
5.375
5.375
6.062
7.125 |
4
4
4
4 |
4
4
4
4.5 |
7
7
7
8.125 |
6
6
6
6 |
4.5
4.5
4.5
5.5 |
8
8
8
9.125 |
6
6
6
6 |
6.5
6.5
6.5
7.5 |
10
10
10
11.25 |
8
8
8
8 |
8
8
8
9 |
12.125
12.25
12.25
13.25 |
2
2 1/2
3
4 |
750
920
1060
1680 |
150
184
212
336
|
4
4
4
4 |
2.5
2.5
3
4 |
5
5.5
6.187
7.25 |
4
4
4
4 |
3
4
4
4.5 |
6.0625
7.125
7.125
8.25 |
4
4
4
4 |
4
4.5
4.5
5.5 |
7.125
8.125
8.125
9.25 |
4
4
4
4 |
4.5
5.5
5.5
6.5 |
8.125
9.125
9.125
10.25 |
6
6
6
6 |
5.5
6.5
6.5
7.5 |
9.125
10.125
10.125
11.375 |
6
6
6
6 |
7.5
8
8
9 |
11.25
12.25
12.375
13.375 |
8
8
8
8 |
9
9.5
9.5
10.5 |
13.25
14.5
14.625
15.625 |
5
6
8
10 |
2100
2550
3400
4000 |
420
510
680
800
|
4
4
4
4 |
4.5
5.5
7.5
9 |
8.5
9.5
11.625
13.875 |
4
4
4
4 |
5.5
6.5
8
9.5 |
9.5
10.5
12.625
15.125 |
4
4
4
4 |
6.5
7.5
9
10.5 |
10.5
11.625
13.625
16.125 |
4
4
6
6 |
7.5
8
9.5
11 |
11.625
12.625
14.875
17.125 |
6
6
6
6 |
8
9
10.5
12 |
12.625
13.625
15.875
18.125 |
6
6
6
6 |
9.5
10.5
12
13 |
14.875
15.875
18.125
20.125 |
8
8
8
8 |
11
12
13
14.5 |
16.875
17.875
20.125
22.125 |
12
14
16
18 |
4400
5000
5800
6400 |
880
1000
1160
1280
|
4
4
4
4 |
10.5
11
12.5
14 |
16.125
17.125
19.375
21.375 |
4
4
4
4 |
11
12
13
14.5 |
17.125
18.125
20.375
22.375 |
4
4
6
6 |
12
12.5
14
15.5 |
18.125
19.125
21.375
23.375 |
6
6
6
6 |
12.5
13
14.5
16 |
19.125
20.125
22.375
24.375 |
6
6
6
6 |
13
14
15.5
16.5 |
20.125
21.125
23.375
25.375 |
6
6
8
8 |
14.5
15.5
16.5
18 |
22.125
23.125
25.375
27.375 |
8
8
8
8 |
16
16.5
18
19.5 |
24.125
25.125
27.375
29.375 |
20
24
30
36
42 |
6800
7200
9400
11000
12400 |
1360
1440
1880
2200
2480
|
4
4
4
4
4 |
15.5
18
22.5
26.5
31 |
23.375
27.375
33.625
40.125
46.125 |
4
4
6
6
6 |
16
19
23
27.5
31.5 |
24.375
28.375
34.625
41.125
47.125 |
6
6
6
6
6 |
16.5
19.5
24
28
32.5 |
25.375
29.375
35.625
42.125
48.125 |
6
6
6
6
6 |
17.5
20.5
24.5
28.5
33 |
26.375
30.375
36.625
43.125
49.125 |
6
6
6
6
6 |
18
21
25
29.5
33.5 |
27.375
31.375
37.625
44.125
50.125 |
8
8
8
8
8 |
19.5
22.5
26.5
31
35 |
29.375
33.375
39.625
46.125
52.125 |
8
8
8
8
8 |
21
24
28
32.5
36.5 |
31.375
35.375
41.625
48.125
54.125 |
|
|
Application:
Model C3100 is designed for use on:
- Cold Water
- Hot Water
- Chilled Water
- Dual Temperature
- Steam
- Air
- Gas
- Vacuum
- Where thermal cycles are infrequent
- Where axial forces are relatively light or in balance.
Intended for Installation on:
Temperature Range: +40°F to +1200°F |
Features
- All pipe sizes
- Easy Installation
- Eliminates welding to pipe
- Overlapping galvanized sheet metal jacket
- Insulating structural inserts for load transfer
- Other I.D.'s and/or O.D.'s available on request
- Bottom-of-pipe to top-of-shield matches insulated supports in "B" series
Performance Test Results on File: Available upon request. |
Material Data:
- C3100: Applicable PSI spec. doc.: No. 209
- Insulation: Calcium Silicate asbestos-free, treated with water repellant.
- Jackets: Galvanized Steel ASTM-527
- Structural Inserts: High-density calcium silicate asbestos-free, treated with water repellant
- Glue: Industrial contact adhesive
- Steel Straps/Base: Carbon Steel ASTM A-36
- Fasteners: ASTM A-307 Plated
- Coating: Primer coated or hot dipped galvanized. Other coatings available upon request.
Formal Submittal Sheets Available |
|
|
|
|
|
|