Insulated Pipe Support · Heavy Duty for Use with Rod Hangers
A9000
A heavy-duty, pre-insulated pipe support for band, ring, and clevis hangers – with insulating structural inserts for load transfer and an overlapping galvanized jacket that minimizes heat loss and condensation, without welding to the pipe.
Talk to a pipe support specialist about your application.
1-707-447-5014General Dimensions & Specifications

Hardware sold separately
Note: For higher load ratings, see B1200

| Pipe Size |
MAXIMUM LOAD RTG. (LBS)In Ring or Clevis Hanger (a) |
|---|---|
| 1/2 | 50 |
| 3/4 | 55 |
| 1 | 80 |
| 1 1/4 | 100 |
| 1 1/2 | 130 |
| 2 | 175 |
| 2 1/2 | 250 |
| 3 | 300 |
| 3 1/2 | 350 |
| 4 | 400 |
| 5 | 550 |
| 6 | 600 |
| 8 | 900 |
| 10 | 1200 |
| 12 | 1450 |
| 14 | 1650 |
| 16 | 1900 |
| 18 | 2150 |
| 20 | 2400 |
| 24 | 2750 |
| TABLE I | |
Contact factory for other dimensions, temperatures, and loads. Available in all insulation thicknesses.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice.
a) To develop maximum load rating use band, ring or clevis hanger with manufacturer’s load rating equal to or greater than values shown in Table I
| Iron Pipe Size |
Insulation Thickness | Copper Tubing Size O.D. |
|||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1/2 | 3/4 | 1 | 1 1/2 | 2 | 2 1/2 | 3 | 3 1/2 | 4 | |||||||||||
| A | B | A | B | A | B | A | B | A | B | A | B | A | B | A | B | A | B | ||
| 1/2 – 1 1/2 | 4 | 24 | 4 | 24 | 4 | 24 | 4 | 24 | 4 | 24 | 4 | 24 | 6 | 24 | 6 | 24 | 6 | 24 | 5/8-1 5/8 |
| 2 | 6 | 24 | 6 | 24 | 6 | 24 | 6 | 24 | 6 | 24 | 6 | 24 | 6 | 24 | 6 | 24 | 6 | 24 | 2 1/8 |
| 2 1/2 – 4 | 6 | 20 | 6 | 20 | 6 | 20 | 6 | 20 | 6 | 20 | 6 | 20 | 9 | 20 | 9 | 20 | 9 | 20 | 2 5/8 – 4 1/8 |
| 5 | 6 | 20 | 6 | 20 | 6 | 20 | 6 | 20 | 9 | 20 | 9 | 20 | 9 | 20 | 5 1/8 | ||||
| 6 – 7 | 6 | 20 | 6 | 20 | 6 | 20 | 6 | 20 | 9 | 16 | 9 | 16 | 9 | 16 | 6 1/8 | ||||
| 8 – 10 | 9 | 16 | 9 | 16 | 9 | 16 | 9 | 16 | 9 | 16 | 9 | 16 | 8 1/8 -10 1/8 | ||||||
| 12 – 18 | 12 | 16 | 12 | 16 | 12 | 16 | 12 | 16 | 12 | 16 | 12 | 16 | 12 1/8 | ||||||
| 20 – 24 | 18 | 16 | 18 | 16 | 18 | 16 | 18 | 16 | 18 | 16 | 18 | 16 | |||||||
| TABLE II “B” = gauge of sheet metal jacket (bottom jacket approx. 2 X ga. of top jacket) | |||||||||||||||||||
Application
Model A9000 is designed for use on:
- Hot water
- Cold water
- Chilled water
- Dual temperature
- Steam
- Air
- Gas
- Vacuum
Intended for installation on:
- Band, ring or clevis pipe hangers
- Flat surfaces, see A7000
- Pipe rolls, see A8000
Temperature Range
Standard: +40°F to +1200°F CalSil Insulation
Note: Up to 1800°F available upon request.
Cryogenic: -275°F to +275°F Urethane Insulation.
Add U after the model number (i.e., A9000U)
Features
- Compact
- Easy installation
- Eliminates welding to pipe
- Overlapping galvanized sheet metal jacket
- Minimizes heat-loss and/or condensation
- Insulating structural inserts for load transfer
- Copper tubing available
- Other I.D.’s and/or O.D.’s available on request
Material Data
| A9000 Spec Doc | Applicable PSI spec. doc.: No. 205 |
|---|---|
| Insulation | Calcium silicate, asbestos-free, treated with water repellant |
| Jackets | Galvanized steel, ASTM A-653 |
| Structural Inserts | High-density calcium silicate, asbestos-free, treated with water repellant |
| Glue | Industrial contact adhesive |
Installation Guide
Model A1000 – A4000 & A9000
1. Position the bottom half of the insulated hanger shield (insulating structural material, sheet metal jacket and load plate where applicable) on the pipe at the applicable support location as shown.
2. Hold the top half of the shield firmly. Open the overlapping sheet metal jacket and gently slide into position the top half of the insulated shield over the bottom half shield as shown.
Model A5000 – A8400
1. When used on a flat surface, position shield so that it is centered on the structural steel.
2. When used with a clevis hanger, position shield symmetrically.
3. When models include heat trace groves, the number and location may vary. Check with design drawings for exact number and location. Ensure that the heat tracing cable is properly positioned inside the grove of the shield.
Completed Assembly Without Load Plate
Completed Assembly With Load Plate
Downloads & resources
Custom Design Request
Need other I.D.'s, O.D.'s, temperatures or loads? Submit a custom design request.
Start Request →Revit RFA 3D Model
A1000 Insulated Pipe Support Revit RFA model for BIM & coordination workflows.
Download 3D Model →