A high-capacity, pre-insulated pipe support for the heaviest A-Series pipe-roll applications – combining insulating structural inserts with an integral load distribution plate to carry substantial loads while accommodating axial movement.

Load Rating1,875–7,450 lbs
Pipe Sizes10" – 42" IPS

Talk to a pipe support specialist about your application.

1-707-447-5014

General Dimensions & Specifications

Model A8400 Insulated Pipe Support

Hardware sold separately
Note: For higher load ratings, see B1200

Section View
A5000 Dimensions

Pipe
Size
MAXIMUM
LOAD RTG.
(LBS)On
Pipe
Roll
A B C Max. Axial
Travel
(Inches)
on
Pipe Roll
10 1875 12 9 1 2 1/4
12 3400 12 9 1 2 1/4
14 3500 12 9 1 2 1/4
16 3950 12 9 1 2 1/4
18 4300 12 9 1 2 1/4
20 4550 12 9 1 2 1/4
24 4950 12 9 1 2 1/4
30 5450 12 9 1 2 1/4
36 6450 12 9 1 2 1/4
42 7450 12 9 1 2 1/4
TABLE I

Contact factory for other dimensions, temperatures, and loads.
Available in all insulation thicknesses.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.

Application

Model A8400 is designed for use on:

  • Hot water
  • Cold water
  • Chilled water
  • Dual temperature
  • Steam
  • Air
  • Gas
  • Vacuum

Intended for installation on:

  • Pipe rolls
  • Flat surfaces see A7400
  • Clevis hangers, see A9000

Temperature Range

Standard: +40°F to +1200°F CalSil Insulation

Note: Up to 1800°F available upon request.

Cryogenic: -275°F to +275°F Urethane Insulation.

Add U after the model number (i.e., A8400U)

Features

  • Compact
  • Easy installation
  • Eliminates welding to pipe
  • Copper tubing sizes available
  • Minimizes heat-loss and/or condensation
  • Insulating structural inserts for load transfer
  • Overlapping galvanized sheet metal jacket
  • Load distribution plate integral with bottom jacket
  • Other I.D.’s and/or O.D.’s available on request

Performance test results on file – available upon request.

Material Data

A8400 Spec Doc Applicable PSI spec. doc.: No. 205
Insulation Calcium silicate, asbestos-free, treated with water repellant
Jackets Galvanized steel, ASTM A-653
Structural Inserts High-density calcium silicate, asbestos-free, treated with water repellant
Load Distribution Plate Carbon steel ASTM A-36
Coating Primer coated or hot-dip galvanized. Other coatings available upon request.
Glue Industrial contact adhesive

Need a formal submittal?

Formal submittal sheets available.


Request a Quote


Custom Design Request

Installation Guide

Installation Model A1000 - A4000 & A9000

Model A1000 – A4000 & A9000

1. Position the bottom half of the insulated hanger shield (insulating structural material, sheet metal jacket and load plate where applicable) on the pipe at the applicable support location as shown.

2. Hold the top half of the shield firmly. Open the overlapping sheet metal jacket and gently slide into position the top half of the insulated shield over the bottom half shield as shown.

Installation Model A5000 - A8400

Model A5000 – A8400

1. When used on a flat surface, position shield so that it is centered on the structural steel.

2. When used with a clevis hanger, position shield symmetrically.

3. When models include heat trace groves, the number and location may vary. Check with design drawings for exact number and location. Ensure that the heat tracing cable is properly positioned inside the grove of the shield.

Completed assembly without load plate

Completed Assembly Without Load Plate

Completed assembly with load plate

Completed Assembly With Load Plate

Downloads & resources

Form
Custom Design Request

Need other I.D.'s, O.D.'s, temperatures or loads? Submit a custom design request.

Start Request →
RFA
Revit RFA 3D Model

A1000 Insulated Pipe Support Revit RFA model for BIM & coordination workflows.

Download 3D Model →
Meet
Schedule a Meeting

Talk through your application with a Pipe Shields engineer.

Book a Time →
Top