Insulated Pipe Support · Extra Heavy Bottom Jacket
A3000
A medium-duty, pre-insulated pipe support for hot, cold, and chilled lines – with a double-thickness bottom jacket that adds structural strength and wear resistance on flat surfaces, hangers, and pipe rolls.
Talk to a pipe support specialist about your application.
1-707-447-5014General Dimensions & Specifications


![]()
![]()
| Oper. Temp. °F |
Mult. Factor “F” |
|---|---|
| 500 | 0.90 |
| 750 | 0.75 |
| 1000 | 0.50 |
| 1200 | 0.30 |
| TABLE III | |
| Pipe Size |
MAXIMUM LOAD RATING (LBS) |
||
|---|---|---|---|
| On Flat Surface (a) (d) |
On Pipe Roll (b) (d) |
In Ring or Clevis Hanger (c) (d) |
|
| 1/2 | 40 | 35 | 45 |
| 3/4 | 45 | 40 | 50 |
| 1 | 65 | 60 | 70 |
| 1 1/4 | 80 | 70 | 90 |
| 1 1/2 | 110 | 100 | 120 |
| 2 | 140 | 125 | 155 |
| 2 1/2 | 165 | 150 | 220 |
| 3 | 200 | 180 | 275 |
| 3 1/2 | 250 | 225 | 325 |
| 4 | 300 | 270 | 375 |
| 5 | 400 | See
A5000 |
475 |
| 6 | 450 | 575 | |
| 8 | 500 | 800 | |
| 10 | 525 | 1100 | |
| 12 | 575 | 1300 | |
| 14 | 600 | 1500 | |
| 16 | 625 | 1700 | |
| 18 | 650 | 1900 | |
| 20 | 700 | 2100 | |
| 24 | 775 | 2400 | |
| TABLE I | |||
Contact factory for other dimensions,
temperatures, and loads.
Available in all insulation thicknesses.
The load ratings represent average values obtained in accordance with accepted
methods and are subject to normal manufacturing variations. Dimensions and ratings
are subject to change without notice.
a) To develop maximum load rating, width of support surface should be at least 1/2 of dimension “A” in Table II.
b) Divide “A” in Table II by 6 to find maximum allowable travel on pipe roll (+/- from centered position).
c) To develop maximum load rating, use band, ring or clevis hanger with manufacturer’s load rating equal to or greater than values shown in Table I.
d) To obtain load ratings for operating temperatures of 500° F and higher, multiply load rating by factor “F” in Table III.
| Iron Pipe Size |
Insulation Thickness | Copper Tubing Size O.D. |
|||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1/2 | 3/4 | 1 | 1 1/2 | 2 | 2 1/2 | 3 | 3 1/2 | 4 | |||||||||||
| A | B | A | B | A | B | A | B | A | B | A | B | A | B | A | B | A | B | ||
| 1/2 – 1 1/2 | 4 | 24 | 4 | 24 | 4 | 24 | 4 | 24 | 4 | 24 | 4 | 24 | 6 | 24 | 6 | 24 | 6 | 24 | 5/8 – 1 5/8 |
| 2 | 6 | 24 | 6 | 24 | 6 | 24 | 6 | 24 | 6 | 24 | 6 | 24 | 6 | 24 | 6 | 24 | 6 | 24 | 2 1/8 |
| 2 1/2 – 4 | 6 | 20 | 6 | 20 | 6 | 20 | 6 | 20 | 6 | 20 | 6 | 20 | 9 | 20 | 9 | 20 | 9 | 20 | 2 5/8 – 4 1/8 |
| 5 | 6 | 20 | 6 | 20 | 6 | 20 | 6 | 20 | 9 | 20 | 9 | 20 | 9 | 20 | 5 1/8 | ||||
| 6 – 7 | 6 | 20 | 6 | 20 | 6 | 20 | 6 | 20 | 9 | 16 | 9 | 16 | 9 | 16 | 6 1/8 | ||||
| 8 – 10 | 9 | 16 | 9 | 16 | 9 | 16 | 9 | 16 | 9 | 16 | 9 | 16 | 8 1/8 – 10 1/8 | ||||||
| 12 – 18 | 12 | 16 | 12 | 16 | 12 | 16 | 12 | 16 | 12 | 16 | 12 | 16 | 12 1/8 | ||||||
| 20 – 24 | 18 | 16 | 18 | 16 | 18 | 16 | 18 | 16 | 18 | 16 | 18 | 16 | |||||||
| TABLE II “B” = gauge of sheet metal jacket (bottom jacket approx. 2 X ga. of top jacket) |
|||||||||||||||||||
Application
Model A3000 is designed for use on:
- Hot water
- Cold water
- Chilled water
- Dual temperature
- Steam
- Air
- Gas
- Vacuum
Intended for installation on:
- Flat surfaces
- Pipe rolls
- Band, ring or clevis pipe hanger
Temperature Range
Standard: +40°F to +1200°F CalSil Insulation
Note: Up to 1800°F available upon request.
Cryogenic: -275°F to +275°F Urethane Insulation.
Add U after the model number (i.e., A3000U)
Features
- Compact
- Easy installation
- Eliminates welding to pipe
- Overlapping galvanized sheet metal jacket
- Minimizes heat loss and/or condensation
- Double thickness bottom jacket for added structural strength and abrasive wear resistance
- Copper tubing sizes available
- Other I.D.’s and/or O.D.’s available on request
- Clamps available (see G-series)
- Clevis available (see PTP fig. 83)
Material Data
| A3000 Spec Doc | Applicable PSI spec. doc.: No. 205 |
|---|---|
| Insulation | Calcium silicate, asbestos-free, treated with water repellant |
| Jackets | Galvanized steel, ASTM A-653 |
| Glue | Industrial contact adhesive |
Installation Guide
Model A1000 – A4000 & A9000
1. Position the bottom half of the insulated hanger shield (insulating structural material, sheet metal jacket and load plate where applicable) on the pipe at the applicable support location as shown.
2. Hold the top half of the shield firmly. Open the overlapping sheet metal jacket and gently slide into position the top half of the insulated shield over the bottom half shield as shown.
Model A5000 – A8400
1. When used on a flat surface, position shield so that it is centered on the structural steel.
2. When used with a clevis hanger, position shield symmetrically.
3. When models include heat trace groves, the number and location may vary. Check with design drawings for exact number and location. Ensure that the heat tracing cable is properly positioned inside the grove of the shield.
Completed Assembly Without Load Plate
Completed Assembly With Load Plate